-1201 (5/04)
GE Zenith’s ZTG Series switches are built for standard
applications requiring the dependability and ease
of operation found in a power contactor switch.
Ratings 40 to 3000 amps (2, 3 or 4 poles)
UL 1008 listed at 480 VAC
CSA certified at 600 VAC
(200-260 amp - 480
V)
IEC listed at 480V
Double throw, mechanically interlocked
contactor mechanism
Electrically operated, mechanically held
Designed for emergency and standby
applications
Available in standard (ZTG) or delayed
transition (ZTGD) models
ZTG switches are equipped with GE Zenith’s
next-generation MX150 microprocessor panel,
which controls the operation and displays the
status of the transfer switch’s position, timers
and available sources. As an embedded digital
controller, the MX150 offers high reliability and
ease of unattended operation across a range of
applications. The MX150 features include:
Timer and voltage/frequency settings
adjustable without disconnection from
the power section
Built-in diagnostics with an LCD display
for immediate troubleshooting
LED
/LCD indicators for ease of viewing
and long life
Nonvolatile memory—clock battery backup
not required for standard switch operation
Processor and digital circuitry isolated from
line voltage
Inputs optoisolated for high electrical
immunity to transients and noise
Communications header for network interface
Fully Approved
UL, CSA and IEC listed
Ringing wave immunity per IEEE 472
(
ANSI C37.90A)
Conducted and Radiated Emissions per
EN55022 Class B (CISPR 11) (Exceeds
EN55011 & MILSTD 461 Class 3)
ESD immunity test per EN61000-4-2 (Level 4)
Radiated
RF, electromagnetic field immunity
test per EN61000-4-3 (ENV50140) 10v/m
Electrical fast transient/burst immunity test
per EN61000-4-4
Surge immunity test per EN61000-4-5
IEEE
C62.41 (1.2 X 50ms, 5 & 8 kV)
Conducted immunity test per
EN61000-4-6
(ENV50141)
Voltage dips and interruption immunity
EN61000-4-11
Design and Construction Features
Close differential 3 phase under-voltage
sensing of the normal source—factory
standard setting 90% pickup, 80% dropout
(adjustable); under-frequency sensing
of the normal source factory setting
95% pickup (adjustable)
Voltage and frequency sensing of the
emergency source—factory standard
setting 90% pickup voltage, 95% pickup
frequency (adjustable)
Test switch (fast test/load/no load)
to simulate normal source failure—
automatically bypassed should the
emergency source fail
Type 1 enclosure is standard—also available
in open style or Types 3R, 4 or 12
ZTG Series
Automatic
Transfer
Switch
Product Bulletin
GE Zenith Controls
e
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Product Bulletin

PB-1201 (5/04)GE Zenith’s ZTG Series switches are built for standardapplications requiring the dependability and easeof operation found in a power con

Page 2 - Standard Features and Options

PB-1201 • Page 2MX150 Control PanelStandard Features (MSTDG Option Pkg.)Additional Standard Features(MEXEG Option Pkg.)(Front View)A3 Auxiliary Contac

Page 3

Page 4 • PB-1201NOTE:For applications requiringadditional options orother configurations,use GE Zenith ZTS Seriesswitches as described inBulletin O-50

Page 4 - Reference Charts

Page 5 • PB-1201Testing StandardsUL, CSA and IEC listed UL 1008, CSA 22.2 No. 178, IEC 947-6-1Ringing wave immunity IEEE 472 (ANSI C37.90A)ESD immunit